Crush Guard - Service - Manitou 160ATJ/180ATJ/200ATJ Adjust DIP Switches

The purpose of this Tech Doc is to help with the adjustment of the DIP switches
The control module contains two sets of DIP switches.
DIP Switch SW2 is used to customise future functionality and at the moment serves no function. The only valid state for DIP Switch SW2 is: all four switches in the OFF position.

Any other switch positions will generate an error.
DIP Switch SW1 is used to configure input signal polarities. SW1 is configured in the factory to match the EWP and should not be altered in the field. Changing the settings of SW1 can cause erroneous fault codes to be produced during operation. If the DIP Switch settings for SW1 have been unintentionally altered contact EQSS for the correct DIP Switch settings for your model EWP.


DIP Switch SW2 must all be set to the OFF position otherwise a fault will be produced disabling the EWP controls

DIP Switch SW1 must not be altered otherwise random faults will be produced disabling the EWP controls