The Boom Angle Sensor is used to determine the inclination of the boom relative to the
initially calibrated machine angle.
The IT01 fault code is most likely to appear if some sort of EQSS module replacement has occurred. If the Display unit has been changed, then boom angle data will have most likely been lost and a Boom Angle Calibration is required.
The remedy that usually clears this fault is the re-calibration of the arm/boom angle. To achieve this task requires the operator to navigate the Gen 3_ITC menu system to the 'Calibrate Boom Angle' function screen.
The navigation path from the Gen 3_ITC main screen is:
1. Press the center 'Enter' button on the 5 button user control
2. Navigate to the 'System Menu'
3. Navigate to the 'Advanced Menu'
4. Enter Password '2 - 8 - 4' and then 'Submit Password'
5. Navigate to the 'Sensor Calibrations'
6. Navigate to the 'Calibrate Boom Angle' function
Proceed with the calibration instructions as displayed on the screen.
Navigate back to the Gen 3_ITC main screen and the IT01 fault should have been cleared and no longer be displayed. If the IT01 fault remains then it's possible that the CDAM has developed a fault.
If the problem persists then contact EQSS support for further guidance.