ITC SWL- Faults - Maintenance

ITC SWL- Faults - Maintenance

The components of the SWL safety system require periodic checks and maintenance to be performed to ensure it remains in working order.
As the SWL is a safety device it's load calibration must be tested every 12 months or when ever changes have occurred to the hydraulic systems. The SWL uses angle transducers plus pressure sensors, installed into the main lifting cylinder, to convert the information into a load reading. The variables in the system can change after a period of time due to a number of different factors, this may result in a higher or lower load reading. e,g. If the counter balance valves have been adjusted or sections of the hydraulic system have been replaced, incorrect load readings can occur. A re-calibration will readjust the load reading for any minor changes in the systems.

With each attachment, lift a known weight to ensure the load reading is within ±100 Kg of the actual weight. If outside this region, a re-calibration must be performed. If re-calibration is required contact an eqss representative to arrange a time to perform the re-calibration.
    • Related Articles

    • ITC SWL- Faults - Fault Codes

      If the light from the SWL system starts flashing red, then it is displaying an error. Error Codes will be based on the red blinking light The following table will describe the various error conditions:
    • ITC SWL- User - Cutout Override

      The SWL safety system will engage the hydraulic cutout if the ITC is beyond it's recommended capacity. The operator is allowed to temporarily override this cutout to allow the boom to be moved back into a safe working region. In order to engage the ...
    • ITC SWL- General - What is it and System Startup

      The SWL system is activated when the ignition is set to accessories or first stage. The ITC SWL is a no display Safe Working Load management system. It uses inclinometers and pressure sensors to generate cutouts when safe working load conditions are ...
    • ITC SWL- Safety - Jump Starting

      Please heed the warning below when jump starting the vehicle Only Jump Start Machine using a Floating Battery – Connect a floating battery of the same type and voltage to the machine by following the instructions in the machine operator manual. If ...
    • ITC SWL- User - Operation

      During normal operation of the unit, the following states will explain the behavior of the unit. Due to the excess pressure during the breakout stage of the bucket, the cutout is disabled until the boom reaches zero degrees to the horizontal.