Gen3_ITC - Installation - Set Time & Sensor Calibration

Gen3_ITC - Installation - Set Time & Sensor Calibration

Notes
Once the installation is complete, the time will need to be set and the sensors will require calibration
Follow the steps below to complete sensor calibrations


Warning
A sensor calibration must be performed once the cable reeler and CPIM have been mounted. If the cable reeler or CPIM have been moved/repositioned a recalibration must be performed
    • Related Articles

    • SFPL - Installation - Sensor Calibration

      Once the installation is complete, the sensors will require calibration. Sensors may also require re-calibration with other maintenance tasks (Display, SD card, Cable reeler replacement) Sensor calibration steps below: A sensor calibration must be ...
    • Gen3_ITC - General - What is a GEN 3 ITC?

      This system has been designed specifically for use with Integrated Tool Carriers (ITC) to cover all relative national and international safety standards. This Tech Doc details system specifications, system functionality, installation requirements, ...
    • ITC SWL- Hitachi - Load Sensor Installation

      The load sensor measures the load attached to the hook of the jib and if the load is greater than the set weight it signals an overload back to the cabin electronics. The load sensor is installed between the jib structure and the hook. Remove the ...
    • OverWatch - User - Session Auto Calibration

      The OverWatch starts sensing the operator from the time the platform’s dead-man trigger is pressed. When the machine is powered, and the system is functional, the operator will see a green light on the OverWatch sensor. This indicates that the ...
    • Gen3 - Calibration - Perform Sensor Calibrations

      Follow the instructions below to access the sensor calibration menu. Press Enter on the user control dial to enter the menu system. Press the arrow buttons to select System Menu. Press Enter to select the menu. Select Advanced Menu Enter the password ...